Meghna Cable

1. Copper Conductor

2. PVC Insulation


PVC Ins. Flexible Cable

Technical Details

Standard: BDS-899, BS-6004

Operating Voltage: 300 / 500 volts

Detail Description or Construction

Plain Annealed Copper Conductor

PVC Insulated

Single Core / Twin Core

Twisted with suitable lay

 

Nominal Cross Sectional

Area of Conductor

mm²

No. and Nominal Diameter of wires no./mm Mazimum DC Resistance of conductor at 20°C ohm/Km Nominal Thickness of Insulation mm Approx Overall Diameter mm Approx Weight of cable kg/mm Current Rating
Bunched and Enclosed in conduits two cables single phase at 35°C amp Clipped to a surface or on a cable tray Bunched & Unenclosed 2 cables single phase at 35°C amp
1X1.0 32/0.20 19.50 0.6 2.70 16.00 9 11
1X1.2 40/0.19 16.44 0.6 2.85 17.00 11 13
1X1.5 30/0.25 13.30 0.7 3.25 23.00 14 16
1X2.0 70/0.19 9.40 0.7 3.50 28.00 16 18
1X2.5 50/0.25 7.98 0.8 3.85 35.50 19 21
1X3.0 110/0.19 5.98 0.8 4.15 43.00 21 23
1X4.0 56/0.30 4.95 0.8 4.50 51.00 23 25
2X1.2 40/0.19 16.44 0.6 2.85 34.00 11 13
2X2.0 70/0.19 9.40 0.7 3.50 56.00 16 18

                                                

Meghna Cable

1. Copper Conductor
2. PVC Insulation

Type: BYA

Technical Details

Standard: BDS-900, BS-6004 & IEC-60227

Operating Voltage: 450 / 750 volts

Detail Description or Construction

Plain Annealed Copper Conductor

PVC Insulated

Non-sheathed single core cable

Application:

Recommended for civil engineering fixed installations i.e. field protected installation in lighting fittings and inside appliances.

Installation: Suitable for install in conduits, raceways, ducts, ladders, walls, direct buried. It is recommended that the installation instructions indicated by the lope electric code or any equivalent, be followed, so that safeguarding of persons and integrity of the will not be affected by deficiencies in the installation.

Nominal Cross Sectional

Area of Conductor

mm²

No. and Nominal Diameter of wires no./mm Mazimum DC Resistance of conductor at 20°C ohm/Km Nominal Thickness of Insulation mm Approx Overall Diameter mm Approx Weight of cable kg/mm Current Rating
Bunched and Enclosed in conduits two cables single phase at 35°C amp Clipped to a surface or on a cable tray Bunched & Unenclosed 2 cables single phase at 35°C amp
1X1.0re 1/1.13 18.10 0.7 2.60 15.00 13 16
1X1.0rm 3/0.65 18.10 0.7 2.90 17.00 13 16
1X1.3rm 3/0.74 14.03 0.7 3.10 20.00 15 19
1X1.5re 1/1.38 12.10 0.7 2.90 21.00 16 20
1X1.5rm 3/0.80 12.10 0.7 3.10 22.00 16 20
1X1.5rm 7/0.52 12.10 0.7 3.10 22.00 16 20
1X2.5re 1/1.78 7.41 0.8 3.50 32.00 22 28
1X2.5rm 7/0.67 7.41 0.8 3.70 32.00 22 28
1X4.0rm 7/0.85 4.61 0.8 4.30 50.00 30 37
1X6.0rm 7/1.05 3.08 0.8 4.95 71.00 38 47
1X10rm 7/1.35 1.83 1.0 6.20 117.00 52 63
1X16rm 7/1.71 1.15 1.0 7.35 178.00 70 85
1X16rm 19/1.04 1.15 1.0 7.40 180.00 70 85
1X25rm 7/2.14 0.727 1.2 9.00 280.00 91 110
1X25rm 19/1.30 0.727 1.2 9.20 282.00 91 110

 

Meghna Cable

1. Copper Conductor

2. PVC Insulation

3. PVC Sheath

Type: BYFY

Technical Details

Standard: BDS-899, BS-6004 & IEC-60227

Operating Voltage: 300 / 500 volts

Detail Description or Construction

Plain Annealed Copper Conductor

PVC Insulated

Two or three core laid flat PVC sheathed overall , color of sheath: Grey/white

 

Application:

Recommended for civil engineering fixed installations i.e. field protected installation in lighting fittings and inside appliances.

Installation: Suitable for install in conduits, raceways, ducts, ladders, walls, direct buried. It is recommended that the installation instructions indicated by the lope electric code or any equivalent, be followed, so that safeguarding of persons and integrity of the will not be affected by deficiencies in the installation.

 

Nominal Cross Sectional

Area of Conductor

mm²

No. and Nominal Diameter of wires no./mm Mazimum DC Resistance of conductor at 20°C ohm/Km Nominal Thickness of Insulation mm Nominal Thickness of Sheath mm Approx Overall Diameter mm Approx Weight of cable kg/mm Current Rating
In conduits single phase at 35°C amp Clipped to a surface or on a cable tray single phase at 35°C amp
2X0.4rm 14/0.19 12.10 0.7 0.9 7.9×4.9 77.00 16 18
2X0.65rm 23/0.19 7.41 0.8 1.0 9.5×5.8 104.00 22 26
2X1.2rm 40/0.19 4.61 0.8 1.0 10.8×6.5 152.50 30 33
2X2.0rm 70/0.19 3.08 0.8 1.1 12.1×7.3 205.00 37 43
2X3.0rm 110/0.19 1.83 1.0 1.2 14.9×8.8 325.50 50 60
2X16rm 7/1.71 1.15 1.0 1.3 17.3×10.0 470.00 66 80
3X1.5rm 7/0.52 12.10 0.7 0.9 10.8×4.9 112.50 15 16
3X2.5rm 7/0.67 7.41 0.8 1.0 13.0×5.8 166.50 20 22
3X4.0rm 7/0.85 4.61 0.8 1.1 15.2×6.7 231.00 28 33
3X6.0rm 7/1.05 3.08 0.8 1.1 17.0×7.5 300.00 35 40
3X10rm 7/1.35 1.83 1.0 1.2 21.0×8.9 490.05 48 54
3X16rm 7/1.71 1.15 1.0 1.3 24.5×10.2 705.00 60 70

 

Meghna Cable

1. Plain Annealed Copper Conductor

2. PVC Insulation

3. PVC Sheath

Type: NYY

Technical Details

Standard: IEC-60502-1 & VDE-0271/3.69

Operating Voltage: 600 / 1000 volts

Detail Description or Construction

Plain Annealed Copper Conductor

PVC Insulated

PVC sheathed single core cable

Application:

Fixed installation, maximum conductor temperature 70°C, Circuit Voltage does not exceed 750 volt.

Installation: Suitable for indoors, outdoors, underground and in water for continuous permissible service voltage of 720/1200 volts. It is recommended that installation instructions indicated by the Local Electric Code, or any equivalent be followed so that the safeguarding of persons and the integrity of the product will not be affected by deficiencies in the installation.

Nominal Cross Sectional

Area of Conductor

mm²

No. and Nominal Diameter of wires no./mm Mazimum DC Resistance of conductor at 20°C ohm/Km Nominal Thickness of Insulation mm Nominal Thickness of Sheath mm Approx Overall Diameter mm Approx Weight of cable kg/mm Current Rating
In conduits single phase at 35°C amp Clipped to a surface or on a cable tray single phase at 35°C amp
1X1.5re 1/1.38 12.10 0.8 1.8 6.80 65.50 27 22
1X1.5rm 7/0.52 12.10 0.8 1.8 6.90 68.00 27 22
1X2.5re 1/1.78 7.41 0.9 1.8 7.40 80.00 36 30
1X2.5rm 7/0.67 7.41 0.9 1.8 7.60 86.50 36 30
1X4rm 7/0.85 4.61 1.0 1.8 8.40 113.50 47 39
1X6rm 7/1.05 3.08 1.0 1.8 8.80 140.50 59 50
1X10rm 7/1.35 1.83 1.0 1.8 9.90 190.50 78 69
1X16rm 7/1.71 1.15 1.0 1.8 10.80 262.00 100 94
1X25rm 7/2.14 0.727 1.2 1.8 12.60 375.50 130 125
1X25rm 19/1.30 0.727 1.2 1.8 12.90 385.50 130 125
1X35rm Min. 6 wire 0.524 1.2 1.8 13.40 472.50 155 160
1X50rm Min. 6 wire 0.387 1.4 1.8 14.80 610.50 185 195
1X70rm Min 12 wire 0.268 1.4 1.8 16.50 846.00 225 245
1X95rm Min 15 wire 0.193 1.6 1.8 18.70 1096.00 270 300
1X120rm Min 18 wire 0.153 1.6 1.8 20.10 1339.00 310 350
1X150rm Min 18 wire 0.124 1.8 1.8 22.00 1641.00 350 405
1X185rm Min 30 wire 0.0991 2.0 2.0 24.50 2026.00 390 460
1X240rm Min 34 wire 0.0754 2.2 2.0 27.20 2640.00 450 555
1X300rm Min 34 wire 0.0601 2.4 2.0 29.90 3250.00 515 640